Inspection History Details
Inspection Status: Approved
Inspection History: ROOF NAILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/07/2005 | ROOF NAILING | Approved | IVRS - Inspection :* | |
| 04/05/2005 | ROOF NAILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NO TEST ON DWV'S 2) WATER LINES MUST BE 12" FROM CAN LIGHTS 3) 1 1/2" VTR MISSING AT KITCHEN SINK 4) W.C. MUST CLEAR 15" ON CENTER FROM OBSTRUCTION 5) NEED LOCATION OF JACUZZI GFCI 6) ROMEX NOT ALLOWED TO BE STAPLED ON IT'S SIDE 7) LADDER TO ROOF NOT SECURED 8) TRUSS CALC'S MUST HAVE A CITY APPROVED STAMP |
|
| 03/30/2005 | ROOF NAILING | Denied | PROVIDE SAFE ACCESS TO ROOF. COMPLY WITH PREVIOUS INSPECTION | |
| 03/29/2005 | ROOF NAILING | Denied | IVRS - Inspection : See detailed listing on site.| 999*1) SHEATHING ON ROOF MUST SPAN 2 BAYS. 2) PROVIDE TRUSS CALCS. 3) PROVIDE ACCESS TO ROOF. |