Permit: T04CM05290

Parcel: 113103760


Addresses:

1334 E SPRING ST

Inspection Status: Approved

Inspection History: ROOF NAILING

Date Description Inspector Results Comments
04/07/2005 ROOF NAILING Approved IVRS - Inspection :*
04/05/2005 ROOF NAILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NO TEST ON DWV'S
2) WATER LINES MUST BE 12" FROM CAN LIGHTS
3) 1 1/2" VTR MISSING AT KITCHEN SINK
4) W.C. MUST CLEAR 15" ON CENTER FROM OBSTRUCTION
5) NEED LOCATION OF JACUZZI GFCI
6) ROMEX NOT ALLOWED TO BE STAPLED ON IT'S SIDE
7) LADDER TO ROOF NOT SECURED
8) TRUSS CALC'S MUST HAVE A CITY APPROVED STAMP
03/30/2005 ROOF NAILING Denied PROVIDE SAFE ACCESS TO ROOF. COMPLY WITH PREVIOUS INSPECTION
03/29/2005 ROOF NAILING Denied IVRS - Inspection :
See detailed listing on site.| 999*1) SHEATHING ON ROOF MUST SPAN 2 BAYS. 2) PROVIDE TRUSS CALCS. 3) PROVIDE ACCESS TO ROOF.