Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - CABLE DROP
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/15/2005 | ELECTRIC - CABLE DROP | Approved | IVRS - Inspection :* | |
| 04/13/2005 | ELECTRIC - CABLE DROP | Denied | IVRS - Inspection : Install 2 ground rods 6 feet apart with a continuous grounding electrode connection Ground rods not installed per 2002 irc 250-53 Next failure will be charged a reinspection fee |
|
| 04/12/2005 | ELECTRIC - CABLE DROP | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) LAYING GROUND RODS IN TRENCH NOT ALLOWED UNLESS THEY CANNOT BE DRIVEN 2) GROUND RODS TO SHALLOW |
|
| 04/11/2005 | ELECTRIC - CABLE DROP | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NO UFER |