Permit: T04CM05285

Parcel: 140376460


Addresses:

6914 S HARRIER LP

Inspection Status: Approved

Inspection History: ELECTRIC - CABLE DROP

Date Description Inspector Results Comments
04/15/2005 ELECTRIC - CABLE DROP Approved IVRS - Inspection :*
04/13/2005 ELECTRIC - CABLE DROP Denied IVRS - Inspection :
Install 2 ground rods 6 feet apart with a continuous grounding electrode connection
Ground rods not installed per 2002 irc 250-53
Next failure will be charged a reinspection fee
04/12/2005 ELECTRIC - CABLE DROP Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) LAYING GROUND RODS IN TRENCH NOT ALLOWED UNLESS THEY CANNOT BE DRIVEN
2) GROUND RODS TO SHALLOW
04/11/2005 ELECTRIC - CABLE DROP Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NO UFER