Permit: T04CM05285

Parcel: 140376460


Addresses:

6914 S HARRIER LP

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
06/06/2005 FRAMING Approved IVRS - Inspection :*
06/02/2005 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) FIRE STOP GARAGE CHASE
2) NAIL SHEAR BLOCK PANELS
3) P-3 SHEAR REQUIRES AB'S AT 16" ON CENTER
4) FIREBLOCK MISSING M.BR
5) DRAFT STOP DUCT WORK
6) LAUNDRY OUT OF WALL
7) NAIL PROTECT PLUMBING
8) NAIL PROTECT WIRES
9) WASTE VENT WITHIN 10 FT OF FRESH AIR INTAKE
10) LOOSE AND MISSING ANCHOR BOLTS
11) 3" SANITARY T NOT ALLOWED IN HORIZONTAL DRAIN M/BATH
12) GAS PRESSURE TEST OK
06/01/2005 FRAMING Denied IVRS - Inspection :
Work is not complete enough to inspect.| 950*
1) STUCCO LATH NOT STAPLED/NAILED AT BOTTOM PLATE OR COMPLETE
2) RED HEAD ANCHOR BOLTS LOOSE
3) HOUSE INSULATED W/O INSPECTION-REMOVE ALL INSULATION