Inspection Status: Approved

Inspection History: EXCAVATION/LAYOUT REBAR & ZON

Date Description Inspector Results Comments
04/08/2005 EXCAVATION/LAYOUT REBAR & ZON Approved IVRS - Inspection :*
1) FOOTING INSPECTION TEST HOLES OK TO BACKFILL
2) PACKOMETER TEST RESULTS SUBMITTED APPEAR OK, BUT NEED TO HAVE REGISTERED ENGINEERS SEAL ON PAPERWORK
3) WILL CHECK AT NEXT INSPECTION
04/06/2005 EXCAVATION/LAYOUT REBAR & ZON Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) ALL FOUNDATIONS COVERED (POURED WITHOUT INSPECTION APPROVAL)
2) DIG DOWN AND EXPOSE ALL FTGS (CORNERS AND HALF-WAY POINTS TO VERIFY DEPTH (TEST INSPECTION HOLES)
3) MASONRY WALLS GROUTED WITHOUT INSPECTION APPROVAL
4) WILL NEED ENGINEERED PACK-O-METER TESTS COMPLETED AND CERTIFIED REGARDING REBAR IN FOOTINGS AND WALLS