Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T04CM05257
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/09/2005 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 01/26/2005 | ELECTRIC - INTERMEDIATE | Partial Approval | ||
| 01/21/2005 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) KITCHEN COUNTER OUTLETS MUST BE WITHIN 24" OF SINK EITHER SIDES AND EVERY 48" THERE AFTER 2) BATHROOM OUTLET MUST BE ON A DEDICATED 20 AMP CIRCUIT 3) SANITARY T CANNOT BE USED AS A DRAIN FITTING. MUST BE A DIRECTIONAL FITTING 4) WATER CLOSET WET VENT MUST BE 2 1/2" OR LARGER 5) DRYER MUST BE 4 WIRE OUTLET 6) WIRES FOR BATH OUTLET MUST BE 12 GAUGE 20 AMP |
|
| 01/19/2005 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* |