Permit: T04CM05246

Parcel: 12801005H

Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Permit Number - T04CM05246

Inspection Description - MECHANICAL - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
10/28/2005 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*PROVIDE A WORKING PLATFORM TO SERVICE FAN COIL. STILL NEED TO CHECK FUSES, DATA PLATE, DUCT SMOKE DETECTORS CONDENSOR. OK FOR CEILING TILES.
10/04/2005 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*INSULATION OK PRIMARY CONDENSTE OK
PROVIDE SECONDARY DRAIN LINE
09/29/2005 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) INSULATE DUCT WORK WITH MINIMUM R5 INSULATION AS PER PLANS AND PER 2000 IECC
2) PROVIDE CONDENSATE DRAIN LINE IN WALL
3) OK TO SHEETROCK SOFFITS
09/28/2005 MECHANICAL - ABOVE CEILING Cancelled IVRS - RI canceled
09/21/2005 MECHANICAL - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) DUCT WORK MUST BE INSULATED WITH MINIMUM R-5 INSULATION. INSULATION USED IS R-4.2
2) PROVIDE CONDENSATE DRAIN LINE IN WALL AS PER PLANS
3) PROVIDE BACKING AROUND CEILING BOXES IN RESTROOM
4) SCHEDULE MECH INTERMEDIATE FOR ANY WORK TO BE COVERED WITH SHEETROCK
5) MECHANICAL ABOVE CEILING FOR WORK ABOVE T-BAR