Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
Permit Number - T04CM05246
Inspection Description - MECHANICAL - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/28/2005 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :*PROVIDE A WORKING PLATFORM TO SERVICE FAN COIL. STILL NEED TO CHECK FUSES, DATA PLATE, DUCT SMOKE DETECTORS CONDENSOR. OK FOR CEILING TILES. | |
10/04/2005 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :*INSULATION OK PRIMARY CONDENSTE OK PROVIDE SECONDARY DRAIN LINE |
|
09/29/2005 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) INSULATE DUCT WORK WITH MINIMUM R5 INSULATION AS PER PLANS AND PER 2000 IECC 2) PROVIDE CONDENSATE DRAIN LINE IN WALL 3) OK TO SHEETROCK SOFFITS |
|
09/28/2005 | MECHANICAL - ABOVE CEILING | Cancelled | IVRS - RI canceled | |
09/21/2005 | MECHANICAL - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) DUCT WORK MUST BE INSULATED WITH MINIMUM R-5 INSULATION. INSULATION USED IS R-4.2 2) PROVIDE CONDENSATE DRAIN LINE IN WALL AS PER PLANS 3) PROVIDE BACKING AROUND CEILING BOXES IN RESTROOM 4) SCHEDULE MECH INTERMEDIATE FOR ANY WORK TO BE COVERED WITH SHEETROCK 5) MECHANICAL ABOVE CEILING FOR WORK ABOVE T-BAR |