Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - TEMP POWER FOR TEST
Permit Number - T04CM05246
Inspection Description - ELECTRIC - TEMP POWER FOR TEST
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/31/2005 | ELECTRIC - TEMP POWER FOR TEST | Approved | IVRS - Inspection :* | |
10/28/2005 | ELECTRIC - TEMP POWER FOR TEST | Not ready for Inspection | IVRS - Inspection :*M/C CABLE TO BE SUPPORTED AS ENTERING CHASE ( 12") AND AT 6' INTERVALS CONNECTION TO CONCE???? AT 250V OR OVER NEED BOND BUSHINGS 250.97 SUPPORT WIRES TO BE ATTACHED AT BOTH END 300.11 FILL UNUSED OPENINGS IN BOXES SUPPORT VDV CABLING AS PER 725.6 & 800.6 PROVIDE ACCESS PATH TO DISCONNECTION MEANS SUPPORT CONDUIT AS PER CODES. |