Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 06/08/2005 |
PLUMBING - INTERMEDIATE |
|
Approved |
IVRS - Inspection :* |
| 06/06/2005 |
PLUMBING - INTERMEDIATE |
|
Not ready for Inspection |
IVRS - Inspection :* 1) REVISED GAS PIPE DRAWING OK. GAS PRESSURE TEST #60 OK. |
| 06/02/2005 |
PLUMBING - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection :* / OK TO COVER BAR AREA. H2O PIPING OVERHEAD INSTALLED PER REVISED APPROVED PLAN. 1) NEEDS CORRECT SERVICING OF PIPING OVERHEAD. 2) VENT PIPING IN MAIN COOLING WILL REQUIRE RE-TEST. 3) INSTALL GAS PIPING PER APPROVED PLAN. WELDED PIPING REQUIRES 60 PSI TEST. |
| 05/19/2005 |
PLUMBING - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection :* WATER TEST WASTE & VENT THRU ROOF ALL AREAS OK. H20 PIPING IN WALL ALL AREAS EXCEPT BAR & OVERHEAD & WATER HEATER INSTALLATION. 1) NEED CITY APPROVED PLAN FOR H20 SYSTEM THAT REFLECTS YOUR INSTALLATION. |
| 05/18/2005 |
PLUMBING - INTERMEDIATE |
|
Not ready for Inspection |
IVRS - Inspection :* MUST HAVE ACCESS TO APPROVED PLANS & PERMITS FOR INSPECTION. |