Permit: T04CM05238

Parcel: 12801001A


Addresses:

170 S WILMOT RD


Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Permit Number - T04CM05238

Inspection Description - PLUMBING - ROUGH, SOIL

Inspection Status - Approved

Date Description Inspector Results Comments
04/27/2005 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection :* RECEIVED LETTER FROM VAUGHN HILL P.E GIVING OK. FOR NO TRAP PRIMERS TO KITCHEN AREA FLOOR DRAINS.
04/19/2005 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :* 1) INSTALL T/K COPPER UNDERSLAB FOR H20 TO BAR AREA. 2) INSTALL TRAP PRIMERS PER NOTES OR PROVIDE LETTER STAMPED & SEALED FROM ARCH & OWNER STATING FLOORS WILL BE ?? MOPED LIBERALLY. SO FLOOR DRAINS WILL RETAIN T-TRAP SEAL AT P-TRAP. 2" T/K H20 SERVICE INSTALLED UP & OUT OF NORTH WEST CORNER OK. 100 PSI AIR TEST
04/18/2005 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection :*
04/14/2005 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :* PARTIAL APPROVED WATER TEST WASTE & VENT UNDERGROUND LAV AREA 108 & 109 OK
04/12/2005 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :* WATER TEST GREASE WASTE UNDERGROUND OK WATER TEST UNDERGROUND SANITARY DRAINAGE OK EXCEPT. 1) LAVS & FLOOR DRAINS IN ROOMS 108 7 109 REQUIRE CORRECT DRAINAGE FITTING AT DOUBLE WYE LOCATION WITH CORRECT END OF LINE CLEANOUTS. 2) WILL NEED TO VIEW PIPE WRAPS & UNDERSLAB H20 PRIOR TO CONCRETE POUR.
04/08/2005 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection :*