Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - ROUGH, SOIL
Permit Number - T04CM05238
Inspection Description - PLUMBING - ROUGH, SOIL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/27/2005 | PLUMBING - ROUGH, SOIL | Approved | IVRS - Inspection :* RECEIVED LETTER FROM VAUGHN HILL P.E GIVING OK. FOR NO TRAP PRIMERS TO KITCHEN AREA FLOOR DRAINS. | |
04/19/2005 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :* 1) INSTALL T/K COPPER UNDERSLAB FOR H20 TO BAR AREA. 2) INSTALL TRAP PRIMERS PER NOTES OR PROVIDE LETTER STAMPED & SEALED FROM ARCH & OWNER STATING FLOORS WILL BE ?? MOPED LIBERALLY. SO FLOOR DRAINS WILL RETAIN T-TRAP SEAL AT P-TRAP. 2" T/K H20 SERVICE INSTALLED UP & OUT OF NORTH WEST CORNER OK. 100 PSI AIR TEST | |
04/18/2005 | PLUMBING - ROUGH, SOIL | Not ready for Inspection | IVRS - Inspection :* | |
04/14/2005 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :* PARTIAL APPROVED WATER TEST WASTE & VENT UNDERGROUND LAV AREA 108 & 109 OK | |
04/12/2005 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :* WATER TEST GREASE WASTE UNDERGROUND OK WATER TEST UNDERGROUND SANITARY DRAINAGE OK EXCEPT. 1) LAVS & FLOOR DRAINS IN ROOMS 108 7 109 REQUIRE CORRECT DRAINAGE FITTING AT DOUBLE WYE LOCATION WITH CORRECT END OF LINE CLEANOUTS. 2) WILL NEED TO VIEW PIPE WRAPS & UNDERSLAB H20 PRIOR TO CONCRETE POUR. | |
04/08/2005 | PLUMBING - ROUGH, SOIL | Not ready for Inspection | IVRS - Inspection :* |