Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
Inspection Status: Approved
Inspection History: PLUMBING - ROOF DRAINS
| Date |
Description |
Inspector |
Results |
Comments |
| 04/29/2005 |
PLUMBING - ROOF DRAINS |
|
Approved |
IVRS - Inspection :* 1) HANGER CORRECTIONS MADE OK 2) OK TO COVER |
| 04/28/2005 |
PLUMBING - ROOF DRAINS |
|
Not ready for Inspection |
IVRS - Inspection :* |
| 04/26/2005 |
PLUMBING - ROOF DRAINS |
|
Not ready for Inspection |
IVRS - Inspection :* HANGERS AND SUPPORTS: EACH CHANGE OF DIRECTION-EACH CHANGE OF ELEVATION- AT THE END OF BRANCHES- THEN-NO MORE THAN FOUR FEET BETWEEN HANGERS. NO EXCEPTIONS |