Permit: T04CM05222

Parcel: 10609062C

Inspection Status: Approved

Inspection History: ELECTRIC - TEMPORARY SERVICE

Date Description Inspector Results Comments
05/13/2005 ELECTRIC - TEMPORARY SERVICE Approved IVRS - Inspection :*LAY IN LITE FIXTURES MUST BE MECHANICALLY FASTENED TO CEILING T -GRID. THEY MAY BE SCREWED IN WITH ONE SCREW AT CENTER OF FIXTURE AT EACH END. YOU MAY ALSO USE FACTORY MADE CLIPS. 2) FIXTURE CONNECTING MC CABLES / WHIPS LONGER THAN 6" FEET MUST SUPPORT FROM WIRES INSTALLED FOR THE PURPOSE. DO NOT USE GRID SUPPORT WIRES TO SUPPORT CABLES. RECALL WHEN COMPLETED. DO NOT TILE.