Permit: T04CM05221

Parcel: 12510070A

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T04CM05221

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
01/18/2005 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
01/14/2005 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
The fixtures are not per plans and specifications.| 250*
1) THE SEISMIC WIRES MUST ATTACH TO THE CORNER HOLES PROVIDED AT THE TOP OF THE FIXTURE
2) THE CLIPS ON THE FIXTURE MUST BE INSTALLED SO THAT THE "CLAW" OF THE CLIP ENGAGES THE TOP BULB OF THE "TEE" BAR
3) ALTERNATE METHOD: YOU MAY SCREW THE FIXTURE TO THE GRID-ON SCREW CENTER-EACH END
4) COVER "J" BOXES