Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/18/2005 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 01/14/2005 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : The fixtures are not per plans and specifications.| 250* 1) THE SEISMIC WIRES MUST ATTACH TO THE CORNER HOLES PROVIDED AT THE TOP OF THE FIXTURE 2) THE CLIPS ON THE FIXTURE MUST BE INSTALLED SO THAT THE "CLAW" OF THE CLIP ENGAGES THE TOP BULB OF THE "TEE" BAR 3) ALTERNATE METHOD: YOU MAY SCREW THE FIXTURE TO THE GRID-ON SCREW CENTER-EACH END 4) COVER "J" BOXES |