Permit: T04CM05208

Parcel: 140376660


Addresses:

6889 S HARRIER LP

Inspection Status: Approved

Inspection History: EXT METAL CLIPS/EXT SHEATHING

Date Description Inspector Results Comments
05/09/2005 EXT METAL CLIPS/EXT SHEATHING Approved IVRS - Inspection :*
05/06/2005 EXT METAL CLIPS/EXT SHEATHING Partial Approval IVRS - Inspection :*
1) NO CHANGE
05/03/2005 EXT METAL CLIPS/EXT SHEATHING Partial Approval IVRS - Inspection :* 1) SOUTH WALL EAST HOLD DOWN NOT INSTALLED AT LOCATION SPECIFIED ON PLAN. 5TH FAILURE. NOTE: HOLD DOWN MUST BE ATTACHED TO FULL LENGTH DOUBLE STUDS.
05/02/2005 EXT METAL CLIPS/EXT SHEATHING Partial Approval IVRS - Inspection :* SOUTH WALL, EAST HOLD DOWN NOT INSTALLED
04/11/2005 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) ONE ANCHOR BOLT NUT NOT TOUGHING WASHER
2) TWO ANCHOR BOLTS HAVE OVERBORED PLATES WITH SMALL WASHERS
04/07/2005 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) ANCHOR BOLT LOOSE ENTRY COLUMNS ALSO MISSING REMOVE SHEATHING TO FULL INSPECT
2) SOUTH WALL EAST HOLDOWN NOT INSTALLED
3) OK TO LATH HOUSE NOT ENTRY COLUMNS
04/06/2005 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) SOUTH HOLDOWN NOT INSTALLED. INSTALL RETRO-FIT
2) DBL 2 X POST REQUIRED UNDER GIRDER TRUSS
3) NO LADDER ACCESS TO ROOF