Inspection History Details
Inspection Status: Approved
Inspection History: EXT METAL CLIPS/EXT SHEATHING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/09/2005 | EXT METAL CLIPS/EXT SHEATHING | Approved | IVRS - Inspection :* | |
| 05/06/2005 | EXT METAL CLIPS/EXT SHEATHING | Partial Approval | IVRS - Inspection :* 1) NO CHANGE |
|
| 05/03/2005 | EXT METAL CLIPS/EXT SHEATHING | Partial Approval | IVRS - Inspection :* 1) SOUTH WALL EAST HOLD DOWN NOT INSTALLED AT LOCATION SPECIFIED ON PLAN. 5TH FAILURE. NOTE: HOLD DOWN MUST BE ATTACHED TO FULL LENGTH DOUBLE STUDS. | |
| 05/02/2005 | EXT METAL CLIPS/EXT SHEATHING | Partial Approval | IVRS - Inspection :* SOUTH WALL, EAST HOLD DOWN NOT INSTALLED | |
| 04/11/2005 | EXT METAL CLIPS/EXT SHEATHING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) ONE ANCHOR BOLT NUT NOT TOUGHING WASHER 2) TWO ANCHOR BOLTS HAVE OVERBORED PLATES WITH SMALL WASHERS |
|
| 04/07/2005 | EXT METAL CLIPS/EXT SHEATHING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) ANCHOR BOLT LOOSE ENTRY COLUMNS ALSO MISSING REMOVE SHEATHING TO FULL INSPECT 2) SOUTH WALL EAST HOLDOWN NOT INSTALLED 3) OK TO LATH HOUSE NOT ENTRY COLUMNS |
|
| 04/06/2005 | EXT METAL CLIPS/EXT SHEATHING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SOUTH HOLDOWN NOT INSTALLED. INSTALL RETRO-FIT 2) DBL 2 X POST REQUIRED UNDER GIRDER TRUSS 3) NO LADDER ACCESS TO ROOF |