Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T04CM05196
Inspection Description - FRAMING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/23/2005 | FRAMING | Approved | IVRS - Inspection :* | |
02/22/2005 | FRAMING | Partial Approval | IVRS - Inspection :* 1) OK TO INSULATE. DO NOT COVER REPAIR AREAS 2) PROVIDE ENGINEERS APPROVED DETAIL FOR CONNECTING GARAGE SHEARWALL TO DBL TRUSS 3) ANCHOR BOLT MISSING NORTH WALL 4) ANCHOR BR DIAGONAL WALL |
|
02/18/2005 | FRAMING | Partial Approval | IVRS - Inspection :* 1) INSTALL BEHIND TUB/SHOWER 2) BLOCK SHOWER SIDES 3) HALL BATH, LAV WET VENTING IS LIMITED TO TRAP ARMS, ONLY NOT DRAINS, AND TRAP TO BE SAME SIZE AS TRAP ARM, DON'T INSTALL 2" PIPE |
|
02/16/2005 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) GAS LINE TO BE MOVED AT KITCHEN, RETEST 2) NO TEST ON DWV'S 3) NAIL PROTECT ABS AT MASTER TOILET 4) INSULATE BEHIND SHOWER AND TUB 5) FIRE BLOCKS MISSING AT KITCHEN 6) SEAL CONDUIT F/ELECTRICAL ISLAND AT OUTSIDE WALL 7) STOPPED INSPECTION |