Inspection Status: Approved
Inspection History: MECHANICAL - HOODS
| Date |
Description |
Inspector |
Results |
Comments |
| 02/16/2005 |
MECHANICAL - HOODS |
|
Approved |
|
| 02/15/2005 |
MECHANICAL - HOODS |
|
Partial Approval |
IVRS - Inspection :* |
| 02/09/2005 |
MECHANICAL - HOODS |
|
Partial Approval |
IVRS - Inspection :* PROVIDE LISTING FOR FRP WALL COVERING BEHIND HOOD. PLANS DO NOT SHOW TYPE I DUCT SIZE. REVISE DRAWING TO SHOW ADEQUATE SIZING. EXTEND SEWER VENTS 2' ABOVE MAKE UP AIR UNIT. PROVIDE CONDENSATE TO AN APPROVED LOCATION. CHECHED GREASE DUCT O.K TO FIRE WRAP. |
| 02/07/2005 |
MECHANICAL - HOODS |
|
Not ready for Inspection |
IVRS - Inspection :* NOT READY |