Permit: T04CM05173

Parcel: 117142280


Addresses:

620 S 6TH AV

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
06/15/2005 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :* 1) ALL CORRECTIONS HAVE BEEN MADE. 2) OK FOR DRY WALL.
06/14/2005 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999* 1) WATER HEATER PIPING TO BE INSTALLED PER YOUR PLAN SIZING. 2) READ YOUR SPEC NOTE # 12 THIS IS NOT WHAT YOU HAVE INSTALLED. IN WALL PIPING REQUIRES INSULATION ALSO. 3) CONDENSATE DRAIN FROM WATER HEATER IS TO BE GRAVITY DRAIN WITH APPROVED MATERIALS. 4) WATER HEATER PIPING IS REQUIRED TO BE SUPPORTED & SO??RED PROPERLY. 5) WATER HEATER VENT TO BE SUPPORTED PROPERLY. PVC REQUIRES PRIMER THEN GLUE FOR CONNECTION OF FITTINGS TO PIPE.
06/09/2005 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1) SEE NOTES FROM 6/7/05 INSPECTION
2) SECURE SHOWER VALVES PROPERLY
06/07/2005 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*