Inspection Status: Approved
Inspection History: PLUMBING - ROUGH, SOIL
| Date |
Description |
Inspector |
Results |
Comments |
| 07/15/2005 |
PLUMBING - ROUGH, SOIL |
|
Approved |
IVRS - Inspection :* |
| 05/10/2005 |
PLUMBING - ROUGH, SOIL |
|
Partial Approval |
IVRS - Inspection :* 1) SOIL WATER TEST IS OK. 2) P.O.C OF NEW BLDG DRAIN TO EXSISTING BLDG DRAIN IS OK. 3) NOTE: FLOOR DRAINS REQUIRE TRAP PRIMERS. OWNER HAS THE OPTION OF PROVIDING A LETTER FROM THE ARCHITECT STATING THAT THE FLOOR WILL MOPED FREQUENTLY TO KEEP THE TRAP SEAL PRIOR TO THE NEXT INSPECTION. |