Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/07/2005 | FRAMING | Approved | IVRS - Inspection :* | |
| 04/04/2005 | FRAMING | Denied | IVRS - Inspection : Work is not complete enough to inspect.| 950* 1) ANCHOR BOLTS LOOSE THROUGHOUT 2) FIRESTOP CHASE IN GARAGE 3) HOLDOWN MORE THAN 8" FROM END OF GARAGE SHEARWALL. BOLT TO SHORT 4) W/H "B" VENT WITHIN 1" OF COMBUSTIBLE MATERIAL 5) 2" DRAIN AT KITCHEN DOES NOT HAVE 1/4" PER FOOT SLOPE. FLAT, ALSO 3" 6) STOPPED INSPECTION, TO MANY ITEMS 7) SUPERINTENDENT TO INSURE HOUSE IS COMPLETE PRIOR TO NEXT INSPECTION |