Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T04CM05154
Inspection Description - FRAMING
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/12/2005 | FRAMING | Approved | IVRS - Inspection :* | |
| 04/07/2005 | FRAMING | Not ready for Inspection | IVRS - Inspection :* 1) SILL HT MAX 44" 2) ALL #6678 AHUS HANGERS REQUIRE 16 COMMON 3) STUCCO LATH NOT APPROVED YET |
|
| 04/01/2005 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) COMPLY WITH 10/SD4, 21/SD4, 11/SD4 2) BLOCK REGISTER AT POWDER ROOM 3) SMOKE DETECTOR LESS THAN 36" FROM REGISTERS 4) OVERSPANS THROUGHOUT 5) SHEAR ABOVE PATIO NOT NAILED 6) HUS 26 HANGERS WRONG NAILS BEING USED 7) SEAL ALL PENETRATIONS FROM 1ST TO 2ND FLOOR 8) DRAG TRUSS NOT ATTACHED TO TOP PLATES AS PER PLAN 9) 7/SD3 NOT PER PLAN 10) STOPPED INSPECTION |