Permit: T04CM05144

Parcel: 116193660


Addresses:

525 N BONITA AV


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T04CM05144

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
02/27/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
02/23/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
INSPECTION FOR INTERIOR ONLY
1. EMERGENCY LIGHTS NOT WORKING
2. HAVE SEVERAL LOOSE RECEPTACLES
3. CHECK PROPER USE OF DIMMERS
(PROVIDE INSTALLATION SHEET)
02/21/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
INSPECTION FOR ROOFTOP EQUIPMENT ONLY
1. GROUND ALL DISCONNECTS
2. SECURE ALL DISCONNECTS & RACEWAYS TO STRUCTURE
3. PHASING NOT CORRECT HP-9, HP-8
4. FUSE SIZE NOT CORRECT HP-8, HP-4, HP-2, HP-1
5. USE EQUIPMENT GROUND TO GROUND J-BOXES, NO INSULATION UNDER SCREW.
6. FLEX OUT OF W.P 2 GANG IS TRIP HAZ/NOT PROPERLY SECURED.
7. DATA ROOM CONDENSOR DOES NOT HAVE PROPER VOLTAGE SUPPLY, EQUIPMENT NOT IDENTIFIED, NOT PROPERLY FUSED, ETC.
8. ALL UNIT DATA PLATES TO BE VISIBLE/ACCESSIBLE
9. MAKE SURE ALL IS PROPERLY IDENTIFIED IN PANEL DIRECTORY'S