Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T04CM05144
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/27/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
02/23/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* INSPECTION FOR INTERIOR ONLY 1. EMERGENCY LIGHTS NOT WORKING 2. HAVE SEVERAL LOOSE RECEPTACLES 3. CHECK PROPER USE OF DIMMERS (PROVIDE INSTALLATION SHEET) |
|
02/21/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* INSPECTION FOR ROOFTOP EQUIPMENT ONLY 1. GROUND ALL DISCONNECTS 2. SECURE ALL DISCONNECTS & RACEWAYS TO STRUCTURE 3. PHASING NOT CORRECT HP-9, HP-8 4. FUSE SIZE NOT CORRECT HP-8, HP-4, HP-2, HP-1 5. USE EQUIPMENT GROUND TO GROUND J-BOXES, NO INSULATION UNDER SCREW. 6. FLEX OUT OF W.P 2 GANG IS TRIP HAZ/NOT PROPERLY SECURED. 7. DATA ROOM CONDENSOR DOES NOT HAVE PROPER VOLTAGE SUPPLY, EQUIPMENT NOT IDENTIFIED, NOT PROPERLY FUSED, ETC. 8. ALL UNIT DATA PLATES TO BE VISIBLE/ACCESSIBLE 9. MAKE SURE ALL IS PROPERLY IDENTIFIED IN PANEL DIRECTORY'S |