Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - CONSTRUCTION POWER
Permit Number - T04CM05144
Inspection Description - ELECTRIC - CONSTRUCTION POWER
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/25/2007 | ELECTRIC - CONSTRUCTION POWER | Approved | IVRS - Inspection :* 1) SUBJECT TO LETTER OF TORQUE-CONTR. WILL FAX-ORIGINAL ON SITE. RECEIVED ON 01/26/07 |
|
01/24/2007 | ELECTRIC - CONSTRUCTION POWER | Denied | IVRS - Inspection : The service is not per code.| 210* 1. INSTALL ALL FEEDER FUSES - NEC 310 2. BOND SERVICE SECONDARY RACEWAYS - NEC 250.92 3. PROTECT FEEDERS OUT OF PVC - NEC 352.46 4. BOND METAL PIPING (WATER & SPRINKLER) TO SERVICE - NEC 250.104 5. PROVIDE LETTER OF TORQUE FOR SERVICE. |
|
01/22/2007 | ELECTRIC - CONSTRUCTION POWER | Not ready for Inspection | IVRS - Inspection :* |