Permit: T04CM05140

Parcel: 114462070

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
01/04/2005 MECHANICAL - FINAL Approved IVRS - Inspection :*APPROVED
12/27/2004 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*/I RESPECTED FIRE DAMPERS IN SHAFT. OK TO COVER. OK FOR TEMP C/O
12/22/2004 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*/IDENTIFY UNITS WITH UNIT NUMBERS. LABEL FAN COIL PANEL FOR FIRE DAMPER ACCESS. IDENTIFY CIRCUIT BREAKERS. PROVIDE FUSES FOR FAN COIL & CONDENSORS.
PROVIDE PROTECTION AROUND REFER LINES AT CONNECTION TO FAN COILS. FIRE DAMPERS NOT INSTALLED IN RATED ASSEMBLY. INSTALL DAMPERS PER MANUFACTURES SPECS. PROVIDE ANGLE IRON FRAMES. EXPOSE OPENING THROUGH FLOOR FOR INSPECTION. PROVIDE INSTALL INSTRUCTIONS