Permit: T04CM05139

Parcel: 103190750


Addresses:

2941 N MECHICA CT


Inspection Status: Approved

Inspection History: FRAMING

Permit Number - T04CM05139

Inspection Description - FRAMING

Inspection Status - Approved

Date Description Inspector Results Comments
03/17/2005 FRAMING Approved IVRS - Inspection :*
03/16/2005 FRAMING Not ready for Inspection IVRS - Inspection :*
1) CANCELLED PER CONTRACTOR
03/15/2005 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) INSTALL GUAGE POTABLE H20, PRESSURIZE TO 80-POUNDS
2) SEAL ALL PENETRATIONS THROUGH PAPER BOTH HOUSES
3) INSTALL PLATE BOLTS WITHIN 12" EACH END BOTTOM PLATES
4) NEED TRUSS SPECS
5) STOPPED INSPECTION
02/23/2005 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999* 1) STRAP PLB, ELECTRIC THROUGHT 2) REMOVE LATHE TO INSPECT 1025 3) INSTALL GAUGE RE PRESSURIZE THE LINES 4) STOPPED INSPECTION