Permit: T04CM05127

Parcel: 12412010A


Addresses:

1010 E BROADWAY BL


Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T04CM05127

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
01/03/2005 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*APPROVED
12/28/2004 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) VDV CABELING TO BE 725.2 & 800.2 AND 725.6 & 800.6
2) M/C CONNECTOR MISSING SNAP RING
3) ? NOT ALLOWED FOR SUPPORT
5) OK BATHROOMS
12/22/2004 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) LETTER FROM J.H. VAN BUREN, ENGINEER RECEIVED AND WILL BE FORWARDED TO OUR RECORDS SECTION
12/21/2004 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :DENIED. SECURE A LETTER FROM MR. JAN VAN BUREN, THE ENGINEER OF RECORD, ALLOWING THE USE OF MC CABLE ON THIS PROJECT.