Permit: T04CM05122

Parcel: 138230060


Addresses:

643 W CALLE MEDINA

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
12/14/2004 FRAMING Approved IVRS - Inspection :*
11/30/2004 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) GAS LINE JOINTS MUST BE PRIMED AND TAPED UNDER GROUND
2) SHUT OFF VALVE REQUIRED BEFORE UNION IN GAS LINE
3) LAUNDRY MUST BE 2" DRAIN AND STAND PIPE WITH TRAP BETWEEN 6" AND 18" OF FLOW
4) NAIL PROTECT PLUMBING AND ELECTRIC WITHIN 1 1/4" OF STUD SURFACES
5) METAL DRYER DUCT REQUIRED IN WALL CAVITY
6) FURR OUT AROUND ELECTRIC HOME RUNS
11/24/2004 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*