Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/20/2007 | FRAMING | Approved | IVRS - Inspection :* | |
| 05/15/2007 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PROVIDE 1" CLEARANCE B-VENT FROM COMBUSTIBLES 2) TERMINATE MASTER BATH EXHAUST FAN TO EXTERIOR 3) INSULATE ALL "Y" FITTINGS DUCT WORK R-5 4) REPAIR OVER KNOTCH DBL TOP PLATE AT GAS LINE MASTER CLOSET 5) SECURE GAS LINE IN ATTIC 8' ON CENTER 6) TERMINATE EXHAUST FAN SECONDARY BATH TO EXTERIOR 7) NAIL PROTECT ABS THROUGHOUT WITH LESS THAN 1 1/2" CLEARANCE 8) EXPOSE GAS BOND TO EXTERIOR 9) PROVIDE ATTIC ACCESS PER PLAN 10) MISSING HIGH/LOW COMBUSTION RELIEF WATER HEATER CLOSET 10 X 10 PER PLAN 11) MAIN HOUSE ONLY-STOPPED INSPECTION |
|
| 05/07/2007 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 11/07/2006 | FRAMING | Not ready for Inspection | IVRS - Inspection :* 1) NEED KITCHEN PANTRY WALL ELECTRIC, HALL BATH AND VENT FANS |
|
| 04/26/2006 | FRAMING | Not ready for Inspection | IVRS - Inspection :* | |
| 02/14/2006 | FRAMING | Not ready for Inspection | IVRS - Inspection :* 1) OWNER NEEDS TO KEEP PERMIT ACTIVE |