Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/01/2005 | ELECTRIC - FINAL | Approved | IVRS - Inspection :*OK FINAL | |
| 03/31/2005 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) METAL DUCT TAPE NOT APPROVED FOR SEALING-USE SHEET METAL PLATES. 2) USE APPROVED GROUND SCREW OR CLIP FOR BATH LIGHT-NOT WOOD SCREW. 3) NEED LETTER FROM ARCHITECT FRO ITEMS # 9, 10, 11 | |
| 03/25/2005 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) REPLACE DRYER PLUG AND COVER INTO BOX 2) OUTLET SPACING ALONG KITCHEN COUNTER TO BE AS PER CODE 210.52 3) PLEASE VERIFY 2ND GFI CIRCUIT AT KITCHEN COUNTER 4) BOXES MORE THAN 1/4" FROM BOX TO SURFACE TO USE APPROVED EXTENDER RING 314.20 5) SMOKE DETECTORS LOCATION TO BE AS PER MANUFACTURERS INSTRUCTIONS 6) BATH FIXTURE TO BE MADE UP IN BOX-FULLY COVER BOX, FILL UNUSED OPENINGS IN FIXTURE 7) WHERE IS REAR RECEPTACLE AS PER PLANS AND CODE 8) TIGHTEN LOOSE CARFLEX FITTINGS 9) PLANS CALL FOR A 20 AMP CIRCUIT FOR A/C-YOU HAVE 30 AMPS 10) WHERE IS HALL LIGHTS AND SWITCHES AS PER PLANS 11) KITCHEN ABOVE SINK LIGHTS AND SWITCH |
|
| 03/10/2005 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* LOCKED NO ACCESS | |
| 11/30/2004 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :*/ 1) CHECK KITCHEN BOX GROUND MAKE-UP ON FINAL |