Permit: T04CM05111

Parcel: 12212253C


Addresses:

4340 E LEE ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
04/01/2005 ELECTRIC - FINAL Approved IVRS - Inspection :*OK FINAL
03/31/2005 ELECTRIC - FINAL Partial Approval IVRS - Inspection :* 1) METAL DUCT TAPE NOT APPROVED FOR SEALING-USE SHEET METAL PLATES. 2) USE APPROVED GROUND SCREW OR CLIP FOR BATH LIGHT-NOT WOOD SCREW. 3) NEED LETTER FROM ARCHITECT FRO ITEMS # 9, 10, 11
03/25/2005 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1) REPLACE DRYER PLUG AND COVER INTO BOX
2) OUTLET SPACING ALONG KITCHEN COUNTER TO BE AS PER CODE 210.52
3) PLEASE VERIFY 2ND GFI CIRCUIT AT KITCHEN COUNTER
4) BOXES MORE THAN 1/4" FROM BOX TO SURFACE TO USE APPROVED EXTENDER RING 314.20
5) SMOKE DETECTORS LOCATION TO BE AS PER MANUFACTURERS INSTRUCTIONS
6) BATH FIXTURE TO BE MADE UP IN BOX-FULLY COVER BOX, FILL UNUSED OPENINGS IN FIXTURE
7) WHERE IS REAR RECEPTACLE AS PER PLANS AND CODE
8) TIGHTEN LOOSE CARFLEX FITTINGS
9) PLANS CALL FOR A 20 AMP CIRCUIT FOR A/C-YOU HAVE 30 AMPS
10) WHERE IS HALL LIGHTS AND SWITCHES AS PER PLANS
11) KITCHEN ABOVE SINK LIGHTS AND SWITCH
03/10/2005 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :* LOCKED NO ACCESS
11/30/2004 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*/ 1) CHECK KITCHEN BOX GROUND MAKE-UP ON FINAL