Permit: T04CM05090

Parcel: 140376200


Addresses:

6937 S GOSHAWK DR

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
04/08/2005 FRAMING Approved IVRS - Inspection :*
04/07/2005 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) 3 PT TRUSSES REQUIRE 5 POSTS
2) SOUTH GARAGE H.D. NUT/BOLT TO SHORT
3) FIRE STOP GARAGE AND FLOOR
4) SHIM GIRDER POST
5) SHIM 3 PT TRUSS OVER DIAGONAL WALL
6) BLOCK SHEAR WALL REPAIR
04/04/2005 FRAMING Denied IVRS - Inspection :
Work is not complete enough to inspect.| 950*
1) LVL NOT NAILED AT 4" ON CENTER
2) NAIL PROTECT PLUMBING WITHIN 1 1/4" OF WALL SURFACE
3) RELOCATE WIRES TOUCHING W/H "B" VENT
4) HOLDOWNS NOT INSTALLED GARAGE SHEARWALL DAMAGED
5) ANCHOR BOLTS LOOSE THROUGHOUT
6) STOPPED INSPECTION, TO MANY ITEMS
7) HAVE SUPERINTENDENT MAKE SURE HOUSE IS COMPLETE PRIOR TO NEXT INSPECTION