Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T04CM05071
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/30/2006 | PLUMBING - FINAL | Approved | IVRS - Inspection :* 15 IN HOUSE BACKFLOW CERTIFICATIONS TURNED IN. |
|
05/26/2006 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
05/25/2006 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
05/24/2006 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* DO ALL ITEMS NOT X'ED OUT ABOVE ITEMS #1,3,5,6,8 PROVIDE CORRECT APPROVED PIPING AT FILTER LOCATION FOR WATER INLET & OUTLET. ICE MACHINE SHALL BE DIRECTLY TRAPPED IF OVER 5' |
|
05/19/2006 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PROVIDE CORRECT CLEANOUT FITTINGS & COVERS ON ALL EXTERIOR CLEANOUTS. 2. MAKE MOP SINKS WATER TIGHT AT WALL & FLOOR & ALL FIXTURES. 3. PROVIDE CORRECT DRAIN RECEPTOR FOR SODA/ICE MACHINE DISPENSERS. 4. HAVE ALL APPLIANCE/EQUIPMENT PERTAINING TO PLUMBING CORRECTLY INSTALLED. 5. COMPLETE INSULATION ON HOT & HOT RETURN PIPE. 6. ALL INDIRECT DRAINAGE PIPING SHALL HAVE MINIMUM 1" AIR GAP & RE-SUPPORTED/SECURED PROPERLY. IF OVER 5' SHALL BE DIRECTLY TRAPPED. 7. PROVIDE CORRECT TERMINATION COVER FOR BACKWATER VALVE. 8. EACH CARBONATOR SHALL HAVE ITS OWN BACKFLOW PROTECTION. NEED PIMA COUNTY OK FOR SEWER. |
|
04/19/2006 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* CONTRACTOR HAD QUESTIONS |