Permit: T04CM05071

Parcel: 14044009G


Addresses:

7710 S WILMOT RD


Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T04CM05071

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
05/30/2006 PLUMBING - FINAL Approved IVRS - Inspection :*
15 IN HOUSE BACKFLOW CERTIFICATIONS TURNED IN.
05/26/2006 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
05/25/2006 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
05/24/2006 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
DO ALL ITEMS NOT X'ED OUT ABOVE ITEMS #1,3,5,6,8
PROVIDE CORRECT APPROVED PIPING AT FILTER LOCATION FOR WATER INLET & OUTLET.
ICE MACHINE SHALL BE DIRECTLY TRAPPED IF OVER 5'
05/19/2006 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PROVIDE CORRECT CLEANOUT FITTINGS & COVERS ON ALL EXTERIOR CLEANOUTS.
2. MAKE MOP SINKS WATER TIGHT AT WALL & FLOOR & ALL FIXTURES.
3. PROVIDE CORRECT DRAIN RECEPTOR FOR SODA/ICE MACHINE DISPENSERS.
4. HAVE ALL APPLIANCE/EQUIPMENT PERTAINING TO PLUMBING CORRECTLY INSTALLED.
5. COMPLETE INSULATION ON HOT & HOT RETURN PIPE.
6. ALL INDIRECT DRAINAGE PIPING SHALL HAVE MINIMUM 1" AIR GAP & RE-SUPPORTED/SECURED PROPERLY. IF OVER 5' SHALL BE DIRECTLY TRAPPED.
7. PROVIDE CORRECT TERMINATION COVER FOR BACKWATER VALVE.
8. EACH CARBONATOR SHALL HAVE ITS OWN BACKFLOW PROTECTION.
NEED PIMA COUNTY OK FOR SEWER.
04/19/2006 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
CONTRACTOR HAD QUESTIONS