Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - ROUGH, SOIL
Permit Number - T04CM05071
Inspection Description - PLUMBING - ROUGH, SOIL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/12/2006 | PLUMBING - ROUGH, SOIL | Approved | IVRS - Inspection :* INSTALL OF 2 1/2" RPB AT METER IS OK |
|
03/30/2006 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :* 1/2 COPPER CONTINUED TO ISLAND WATER STATION/AIR STATION STUBBED UP 60 PSI TEST OK |
|
03/28/2006 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :* CONNECTION TO INTERCEPTOR DOWN STREAM, INTERCEPTOR VENT, AND BACK WATER VALVE INSTALLATION DOWN STREAM OF BUILDING SEWER & INTERCEPTOR DISCHARGE PARTICAL PENDING REVISED APPROVED PLAN OF THIS INSTALLATION COVER AT OWN RISK. |
|
03/24/2006 | PLUMBING - ROUGH, SOIL | Denied | IVRS - Inspection : See detailed listing on site.| 999* INVERT OF VENT SHALL BE TAKEN OFF ABOVE THE FLOW LINE OF SEWER. |
|
03/21/2006 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :* 1/2" SOFT UPPR FROM BUILDING EXTERIOR CENTER EAST BY H2O SERVICE VALVE BOX NORTH TO METER LOCATION 60 PSI TEST PARTIAL. WILL SEE CONTINUATION OF THIS TO AIR/WATER STATION AT LATER DATE. |
|
03/16/2006 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :* 2 1/2" PVC SCH 40 YARD WATER PIPING FROM METER LOCATION TO EXISTING SERVICE VALVE 50 PSI WATER TEST OK 1. NEED TO SEE CONNECTION TO METER WITH CORRECT BACKFLOW ASSEMBLY INSTALL. HAVE YOUR ENGINEER PROVIDE INFORMATION ON CORRECT BACKFLOW SIZE. SITE & PLUMBING PAGE ARE IN CONFLICT. |
|
03/15/2006 | PLUMBING - ROUGH, SOIL | Not ready for Inspection | IVRS - Inspection :* PROVIDE MINIMUM 50 PSI AIR OR WATER TEST ON 2 1/2" YARD PIPING. |
|
03/14/2006 | PLUMBING - ROUGH, SOIL | Not ready for Inspection | IVRS - Inspection :* 1. P2 PAGE SHOWS 2 1/2 CW SUPPLY TO BUILDING. SITE PLAN 2A OF 3 SHOWS 1 1/2 RP WITH 1 1/2 SUPPLY TO BUILDING. CODE REQUIREMENT IS RP AND BUILDING SUPPLY TO BE OF EQUAL SIZE. PLEASE PROVIDE CORRECT INFORMATION ON YARD WATER SIZING. 2. PROVIDE MINIMUM 50 PSI AIR OR LINE PRESSURE WATER TEST. |
|
03/02/2006 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :* 4" SITE SEWER FROM BUILDING EXTERIOR & DISCHARGE OF INTERCEPTOR TO AREA OF PUBLIC MANHOLE 5PSI AIR TEST OK 1. NEED TO VIEW CONNECTION TO BUILDING & INTERCEPTOR AND FLEXIBLE CONNECTION WITHIN 3' OF MANHOLE BASE. 4" GREASE WASTE FROM (2) 2" AT BUILDING TO INTERCEPTOR WATER TEST OK 1. NEED TO SEE CONNECTIONS (2) AT BUILDING OK TO COVER INTERCEPTOR |
|
02/23/2006 | PLUMBING - ROUGH, SOIL | Not ready for Inspection | IVRS - Inspection :* | |
02/21/2006 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :* 4TH SDR 35 FROM WYE CONNECTION FOR BUILDING AND GREASE INTERCEPTOR WITH CLEANOUTS AT CORRECT INTERVALS TO AREA OF COMBO FOR PUBLIC SEWER. 1. WILL NEED AIR TEST, VERIFICATION OF GRADE INSPECTION OF BUILDING TIE IN, PUBLIC SEWER TIE IN AND BACKWATER VALVE INSTALL. 2. SHALL REQUIRE AUTHORIZATION TO DISCHARGE INTO NEW 8" PUBLIC SEWER YET TO BE CONSTRUCTED. |
|
02/16/2006 | PLUMBING - ROUGH, SOIL | Not ready for Inspection | IVRS - Inspection :* APPROVED PLAN IS ON SITE. INSTALLATINO IS TO APPROVED PLAN BUT DOES NOT MEET 94 UPC FOR MAXIMUM DISTANCES BETWEEN CLEANOUTS. CLEANOUTS SHALL BE INSTALLED NOT TO EXCEED 100' MAXIMUM INCLUDING RISE TO GRADE. PROVIDE CORRECT TRACER WIRE WITH CLEANOUT PER PIMA COUNTY DETAIL WWM 401. |
|
02/09/2006 | PLUMBING - ROUGH, SOIL | Not ready for Inspection | IVRS - Inspection :* 1. SITE SEWER REQUIRES STAMPED CITY APPROVED PLAN 2. PROVIDE CORRECT TRACER WIRE PER STATE STATUE 3. PROVIDE VERIFICATION OF GRADE FROM SURVEYOR OR ENGINEER 4. PROVIDE AIR OR WATER TEST |
|
12/20/2005 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :* 2 1/2" T/C IS SUPPLIED FOR WATER SERVICE ENTRY STUBBED UP T OUT 10' OF BUILDING 60 PSI AIR TEST OK -- TYPE K IS SPEC. INSTALL FOR SPEC. OR PROVIDE SEALED LETTER FROM ENGINEER GIVING OK FOR T/2 1/2" TO ISLAND ALSO STUBBED OVER AT OWN RISK |
|
11/29/2005 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :*6 PSI AIR TEST ( 2) 2" GREASE WASTE STUB UP & OUT OF BUILDING TO 2' AFF. (1) 2" INTERCEPTOR VENT AIR TEST STUBBED UP & OUT OF BUILDING 2' AFF OK REVISED CITY APPROVED PLAN ON SITE. PRESLAB OK |
|
11/28/2005 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :* | |
11/16/2005 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :* 1) 6" AIR TEST ON UNDERGROUND PER REVISION <1> DATED 9/30/05 QUIZNOS REVIEW, SHALL SERVE AS RED LINE 2) NEED TO SEE REVISED APPROVED PLAN WITH TRAP PRIMERS, TEST ON (2) 2" GREASE WASTE STUBS AND INTERCEPTOR VENT PRIOR TO CONCRETE COVER AT OWN RISK |