Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/17/2005 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 10/12/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*FINISH AL PREVIOUS ITEMS. A RE FEE MAY BE ASSESED IF NOT COMPLETE |
|
| 10/10/2005 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :*FINISH ELECTRIC AS DISCUSSED | |
| 10/06/2005 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* BOXES IN COMBUSTIBLES TO USE APPROVED EXTENDER RINGS ALSO MORE THAN 1/4" FROM BOX TO SURFACE GROUND FIXTURES ONLY ONE CONDUCTOR PER LUG A/C DISCONNECT THIGHTEN LOOSE SEAL TITE FITTINGS TAPE TO ENCIRCLE CONDUCTOR NOT LENGTH WISE. KNOCK OUT COMING OUT BACK PORCH RECEPTACLE COVERS TO BE WEATHER PROOF WETHER OR NOT PLUGGED IN OUTSIDE LIGHT NOT ON PLANS. LIGHT TO MEET LIGHTING ORDINANCE. |