Permit: T04CM05051

Parcel: 106050320


Addresses:

605 W PELAAR DR

Inspection Status: Approved

Inspection History: EXCAVATION/LAYOUT REBAR & ZON

Date Description Inspector Results Comments
03/25/2005 EXCAVATION/LAYOUT REBAR & ZON Approved IVRS - Inspection :*
03/24/2005 EXCAVATION/LAYOUT REBAR & ZON Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) UFER REQUIRES BRASS SCREWS AND CLAMPS
2) MAINTAIN MINIMUM 3" CLEARANCE REBAR TO DIRT
3) GARAGE FOOTINGS REQUIRE VERTICAL REBAR SEE DETAIL 2/2
4) P.A. HOLDOWNS REQUIRE REBAR HORIZONTALLY TIED TO BOTTOM OF HOLDOWNS
03/22/2005 EXCAVATION/LAYOUT REBAR & ZON Not ready for Inspection IVRS - Inspection :*