Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T04CM05050
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/27/2005 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
01/26/2005 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| USE APPROVED SUPPORTING DEVICE TO SUPPORT MC TO BE LISTED, TWISTING SISMEC A FEW TURNS AROUND MC NOT APPROVED |
|
01/21/2005 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* NOTES 1) MC CABEL MUST BE INDEPENDENTLY SUPPORTED DO NOT TIE TO CONDUIT FOR SUPPORT. 2) ONE SISMEC WIRE REQUIRED FOR EACH C? LT. PER NEC, COT ADDENDUMS ALSO J-BOXES. 3) WITH EXCEPTION OF 6' LENGHTS FOR FIXTURE CABLES, M? MUST BE SUPPORTED WITHIN 12'' EACH TERMINATION AND AT 6' INTERVALS |