Permit: T04CM05048

Parcel: 11104218A

Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Date Description Inspector Results Comments
09/01/2005 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
1) OK FOR CEILING TILES
2) SECONDARY DRAINS WILL BE REQUIRED AS PER PLANS
08/30/2005 MECHANICAL - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) STRAPS ON FLEX DUCTS MUST BE MINIMUM 1 1/2" WIDE HANGER STRAP
2) SEE NOTES FROM PREVIOUS INSPECTION. MECHANICAL CONTRACTOR PLEASE READ THE PLANS AND SPECS PRIOR TO PROCEEDING
08/26/2005 MECHANICAL - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) ON FINAL PERMANENTLY IDENTIFY EQUIPMENT
2) STRAP ON SUPPORT FLEX DUCTS FROM BATHROOM EXHAUST AND STRAP UP FLEX DUCTS LAYING ON GRID AND TILES. INSULATE ALL SPIRAL PIPE IN CEILING SPACE AND T WYES. SUPPORT REFER LINES IN MECHANICAL ROOM. FLEX DUCT BLOCKING ACCCESS TO FC 1. PROVIDE A PLATFORM ABOVE THE HARD DUCT TO SERVICE FC1. PLANS CALL FOR SECONDARY DRAIN PANS UNDER FAN COILS
07/21/2005 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) CONDENSATE PIPING, SUSPENDED COPPER TO AIR HANDLER LOCATIONS, DOWN TO FLOOR SINK