Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T04CM05036
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/11/2007 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
12/19/2006 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* BLOWER COMPARTMENT CANNOT BE ACCESSED WITHOUT DISMANTLING THE UNIT. UNIT DOES NOT HAVE CLEARANCE FROM WALL ON ROOF. RECOMMED RELOCATING UNIT & DUCTING OVER TO THE EXISTING LOCATION OR FILE FOR AN APPEAL WITH THE CODE ADMINISTRATOR. |
|
11/21/2006 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* - RELOCATE A/C 1 THERE IS NO ACCESS TO REMOVE BLOWER. - PROVIDE FRESH AIR INTAKES - MARK UNIT DATA PLATE W/PROPER HEAT STRIP INSTALLED & FUSE ACCORDINGLY. TURN FUSES SO THEY CAN BE IDENTIFIED. - PROVIDE A MECHANICAL PLAN & AIR BALANCE REPORT. |