Permit: T04CM05032

Parcel: 133240090


Addresses:

8051 E BROADWAY BL


Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T04CM05032

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
09/22/2005 PLUMBING - FINAL Approved IVRS - Inspection :*
1) PLUMBING FINAL IS OK
2) OK FOR C OF O
09/19/2005 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) SHALL PROVIDE OR EXPOSE C.O. FOR SINK RM #20
2) SHALL HAVE MIN OF 15" OF SIDE WALL CLEARANCE FOR WATER CLOSET IN WOMENS RESTROOM
3) CAN NOT RUN GARBAGE DISPOSAL WITH INDIRECT WASTER. SHALL PROVIDE A DIRECT WASTE CONNECTION OR REMOVE THE DISPOSAL
4) SHALL CAULK ALL FIXTURES
5) SHALL PROVIDE MIN OF (3) SHEET METAL SCREENS PER JOINT @ WATER HTR APPLIANCE COLLAR
6) SHALL SECURE EXPANSION TANK TO WALL. CAN NOT HANG PIPE FROM ANOTHER PIPE
7) SHALL PROVIDE TEST CERTIFICATION FOR ICE MAKER BACKFLOW PREVENTER