Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T04CM05032
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/22/2005 | PLUMBING - FINAL | Approved | IVRS - Inspection :* 1) PLUMBING FINAL IS OK 2) OK FOR C OF O |
|
09/19/2005 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SHALL PROVIDE OR EXPOSE C.O. FOR SINK RM #20 2) SHALL HAVE MIN OF 15" OF SIDE WALL CLEARANCE FOR WATER CLOSET IN WOMENS RESTROOM 3) CAN NOT RUN GARBAGE DISPOSAL WITH INDIRECT WASTER. SHALL PROVIDE A DIRECT WASTE CONNECTION OR REMOVE THE DISPOSAL 4) SHALL CAULK ALL FIXTURES 5) SHALL PROVIDE MIN OF (3) SHEET METAL SCREENS PER JOINT @ WATER HTR APPLIANCE COLLAR 6) SHALL SECURE EXPANSION TANK TO WALL. CAN NOT HANG PIPE FROM ANOTHER PIPE 7) SHALL PROVIDE TEST CERTIFICATION FOR ICE MAKER BACKFLOW PREVENTER |