Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - YARD WTR LINE/TEST
Permit Number - T04CM05032
Inspection Description - PLUMBING - YARD WTR LINE/TEST
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/22/2005 | PLUMBING - YARD WTR LINE/TEST | Approved | ||
07/21/2005 | PLUMBING - YARD WTR LINE/TEST | Partial Approval | IVRS - Inspection :* 1) 1 1/4" YARD WATER SUPPLY IS OK TO BLDG SERVICE OF PARSONAGE BLDG 2) OK TO BACKFILL TRENCH |
|
07/15/2005 | PLUMBING - YARD WTR LINE/TEST | Not ready for Inspection | IVRS - Inspection :* | |
07/14/2005 | PLUMBING - YARD WTR LINE/TEST | Partial Approval | IVRS - Inspection :* WATER TEST ON 2 1/2" YARD LINE FROM METER TO BUILDING OK PLAN CALLS FOR 2 1/2" RPB, 2" IS INSTALLED , PLAN CALLS FOR 1 1/4 TO PARSONAGE BUILDING I" IS TAP OFF 2 1/2", PLEASE SUPPLY LETTER FROM ENGINEER GIVING OK FOR THIS SIZING CHANGE. 1) NEED TO VIEW LANDSCAPING BACKFLOW DEVICE AND CERTIFICATION OF BOTH BACKFLOW DEVICES. 2) NEED TO VIEW TIE IN FOR 1" INTO 1 1/4" EXISTING TO PARSONAGE YARD LINE APP. 30' NORTH OF NEW BUILDING NORTH WEST CORNER. | |
07/13/2005 | PLUMBING - YARD WTR LINE/TEST | Not ready for Inspection | IVRS - Inspection :* | |
03/02/2005 | PLUMBING - YARD WTR LINE/TEST | Partial Approval | IVRS - Inspection :* 1) 2 1/2" COPPER SERVICE STUBBED UP AND OUT 5' NORTH BLDG FACE 70 PSI TEST PARTIAL APPROVAL |