Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T04CM05032
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/20/2005 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
09/02/2005 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) OK TEMP POWER FOR TEST SUBJECT TO BOND 2) CONTRACTOR TO MAINTAIN LOCKOUT TAG OUT TO EQUIPMENT 3) BONDING JUMPER TO BE SIZED PER 250.102 AND 250.66 4) PLEASE PROVIDE A LETTER FOR TORQUE VALVES 5) VERIFY USAGE OF ALUMINIUM GROUND CONDUCTORS TO PANELS |
|
08/31/2005 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) WHEN SUPPORTED CABLES AND CONDUITS TO BE ATTACHED AT BOTH ENDS 300.11 2) DO NOT SUPPORT OFF OF SPRINKLER PIPE 3) SUPPORT CONDUIT WITHIN 3' 4) VDV CABELING TO BE SUPPORTED 725.6 AND 800.6 |