Permit: T04CM05019

Parcel: 11804173D

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
01/14/2005 FRAMING Approved IVRS - Inspection :*
01/13/2005 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) STAIR RISE EXCEEDS 7 3/4"
2) OK TO INSULATE AND DRYWALL ALL BUT STAIR AREA
01/11/2005 FRAMING Denied IVRS - Inspection :
Work is not complete enough to inspect.| 950*
1) DBL TOP PLATE OF P-1 SHEAR CANNOT BE CUT OR NOTCHED. HAVE ENGINEER PROVIDE REPAIR
2) CLIP KITCHEN P-1 SHEAR TO TRUSS WITH 6 A35 CLIPS 5) STAIRS NOT PER 49/AD3
6) DBL TOP PLATE SPLICES CANNOT BE WITHIN 48" OF EACH OTHER
7) 4 X 8 BEAM MUST BEAR ON HANGER IN GARAGE. FILL ALL NAIL HOLES IN HANGER
8) STUD MISSING P-1 SHEARWALL
9) PEX CANNOT BE WITHIN 12" OF CAN LIGHTS
10) STOPPED INSPECTION, TOO MANY ITEMS
01/07/2005 FRAMING Denied IVRS - Inspection :
Work is not complete enough to inspect.| 950*
1) STUCCO LATH MUST BE COMPLETE AND APPROVED PRIOR TO INTERMEDIATES INSPECTION