Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/14/2005 | FRAMING | Approved | IVRS - Inspection :* | |
| 01/13/2005 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) P3 SHEARWALL NOT NAILED TO FLOOR TRUSS AT 4" ON CENTER 2) ITEMS 1, 3, 11, 13 AND 17 FROM 1/11/05 INSPECTION NOT COMPLIED WITH |
|
| 01/11/2005 | FRAMING | Denied | IVRS - Inspection : Work is not complete enough to inspect.| 950* 1) PEX LINES MUST BE WITHIN 1/16" OF FITTING STOP COLLARS. WATER ENTRANCE 2) GARAGE P-3 SHEARWALL REQUIRES NAILS AT 3" ON CENTER AT EDGES AND NAILS MUST BE 3/8" FROM EDGES 3) W/H "B" VENT REQUIRES 1" CLEARANCE TO COMBUSTIBLE MATERIAL 4) PEX MUST BE 6" FROM "B" VENT 5) STAIRS NOT PER 53/AD3 6) RED HEAD ANCHOR BOLTS LOOSE 7) STAIR RISER EXCEEDS 7 3/4" FIRST STEP 8) RISER CHASE GREATER THAN 3/8" NOT ALLOWED 9) FLOOR PANELS NOT T & G JOINED SOUTHWEST BEDROOM 10) NO DWV WATER TEST 2ND FLOOR 11) NAIL PROTECT PLUMBING WITHIN 1 1/4" OF WALL STUD SURFACE 12) FIRESTOP W/H "B" VENT 2ND FLOOR AND CEILING 13) DBL TOP PLATES OVER KNOTCHED. FILL ALL HOLES IN FHA STRAPS 14) PEX MUST BE 12" FROM RECESSED LIGHTS 15) OVERSPAN STUD MISSING 1/2 BATH SHEARWALL 16) FIRE STOP CHASE IN GARAGE 17) HORIZONTAL DWV MUST HAVE 1/4" PER FT PITCH 18) 2ND FLOOR PLATES NOT NAILED PER 1/SD2 OR 2/SD2 19) STOPPED INSPECTION, TOO MANY ITEMS |
|
| 01/07/2005 | FRAMING | Denied | IVRS - Inspection : Work is not complete enough to inspect.| 950* 1) STUCCO LATH MUST BE COMPLETE AND APPROVED PRIOR TO INTERMEDIATES INSPECTION |