Permit: T04CM05013

Parcel: 11708217B


Addresses:

915 S MEYER AV

Inspection Status: Approved

Inspection History: ROOF NAILING

Date Description Inspector Results Comments
03/02/2005 ROOF NAILING Approved IVRS - Inspection :*
1) ROOF VENTS DELETED AND APPROVED BY ENGINEER AND PLAN CHECK WILDAN
2) NEED ENGINEERED SPECIAL INSPECTION ON MBHA BRACKET SKY LIGHTS-WILL CHECK AT INTERMEDIATE
3) REVISED MECH APPROVED BY ENGINEER AND PLAN CHECK WILDAN
4) INSTALL ANCHOR BOLTS 2 X 12 BARGE RAFTER OVER FRONT ENTRY-WILL CHECK AT INTERMEDIATES
02/23/2005 ROOF NAILING Denied IVRS - Inspection :
See detailed listing on site.| 999* 1) PROVIDE ROOF VENTS AS PER APPROVED DRAWINGS 2) ENGINEER OF RECORD MUST APPROVE ?? ANCHORS @ SKY LIGHT-SPECIAL INSPECTION REQ'D AT APOXIED BOLTS. 3) REVISE MECHANICAL PLAN TO MATCH AS BUILD. 4) LEDGER AT FRONT ENTRY MUST BE SECURED