Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 04/12/2005 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection :* |
| 04/11/2005 |
ELECTRIC - FINAL |
|
Not ready for Inspection |
IVRS - Inspection :* 1) LIGHTING NOT AS PER PLANS PLEASE PROVIDE A LETTER FOR THESE CHANGES. 2) PREVENT DIELECTRIC CONTACT WITH COPPER PIPING UNDER COUNTERS. 3) SUPPORT VDV CABELING AS PER 725.6, 760.6, 800.6 4) TRAC LIGHTING NEED SUPPORT WIRES 1/4'. 5) M/C CABLE NOT TO BE SUPPORTED OFF OF OTHER WIRING METHODS ( CONDUITS) 6) SUPPORT FLEX CONDUIT OFF OF GRID. 7) FIXTURES TO BE ATTACHED TO GRID. |