Permit: T04CM05002

Parcel: 10819224A


Addresses:

811 E WETMORE RD


Inspection Status: Approved

Inspection History: POOL/SPA ELECTRIC

Permit Number - T04CM05002

Inspection Description - POOL/SPA ELECTRIC

Inspection Status - Approved

Date Description Inspector Results Comments
07/19/2006 POOL/SPA ELECTRIC Approved IVRS - Inspection :*
07/18/2006 POOL/SPA ELECTRIC Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. POOL LIGHTS NEED TO ALL BE OPERATING AND HAVE GFI PROTECTION.
2. PANEL DIRECTORY IS NOT CORRECTLY LABELED.
07/14/2006 POOL/SPA ELECTRIC Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
STILL NEED TO MAKE CORRECTIONS #1, #2, #3, #6, #8
FROM PREVIOUS INSPECTION.
06/07/2006 POOL/SPA ELECTRIC Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. IDENTIFY PANEL DIRECTORY - NEC 408.4
2. BOND GAS PIPE - NEC 250.104 (B)
3. TIGHTEN ALL BONDING CONNECTIONS - NEC 110/250
4. PROVIDE 3' CLEAR SPACE IN FRONT OF PANEL - NEC 110.26
5. BOND FENCE AROUND POOL - NEC 680.26(B)(5)
6. RECEPTACLES NOT ALLOWED WITHIN 10' OF POOL OR HOT TUB - NEC 680.22 (A)(2)
7. I DO NOT BELIEVE THE CURRENT LOCATION OF THE EMERGENCY SHUT OFF FOR HOT TUB MEETS NEC 680.41
8. CHECK TO SEE IF POOL LUMINAIRE NEEDS GFI PROTECTION (I HAVE NO PLANS ON SITE).
03/06/2006 POOL/SPA ELECTRIC Denied NO ONE ON SITE -- NEED APPROVED PLANS AND GATE UNLOCKED -- CALL AND MAKE ARRANGEMENTS
03/02/2006 POOL/SPA ELECTRIC Partial Approval IVRS - Inspection :*
09/27/2005 POOL/SPA ELECTRIC Partial Approval IVRS - Inspection :* ISOLATE NEUTRAL FROM GROUNDING BUS AT PANEL & BOND GROUNDING BUS.
BOND POOL FENCE
09/26/2005 POOL/SPA ELECTRIC Denied IVRS - Inspection :
See detailed listing on site.| 999*
08/11/2005 POOL/SPA ELECTRIC Partial Approval IVRS - Inspection :*
1) U.G. AS DISCUSSED WITH CARL
12/15/2004 POOL/SPA ELECTRIC Partial Approval IVRS - Inspection :*
1) POOL LIGHTS OK
2) OK TO GUNITE