Permit: T04CM04999

Parcel: 13411362A


Addresses:

8291 E 22ND ST

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
05/05/2005 FRAMING Approved IVRS - Inspection :*
02/08/2005 FRAMING Partial Approval IVRS - Inspection :*OK TO COVER PER ARCHITECT OBSERVATIONS. 1) YOU MUST PROVIDE APPROVED REVISED PLANS PP A2 WALL TYPE@WALL LEGEND EXTERIORS NON STRUCTURAL WALL CALLS FOR 16 GA STUD WALL 16" OC. AS BUILT IS 20 GAGE FLASHING SCRWED BACK TO BACK IN A "2" WITH BASE EMBEDDED IN CONCRETE. PP A3 BULKHEAD DETAIL NOT PER PLAN ?STALLED AS 4" 20 GA STUD FOR VERTS AND HORIZONTAL. NO 2X4 EDGE A BOTTOM ONLY 18 GA CORNER TRACK. 3 # 8 TECH SCREWS AT EACH VERT/??CONNECTION. PP A5 GSN'S NO DOUBLE STUDS@ ??. NO MID HEIGH BRIDGING
02/03/2005 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999* 1) PLEASE READ ALL DETAILS AND GSN'S REGARDING YOUR COLD FORMED STEEL FRAMING. THEN INSTALL PER DETAILS OK REVISE YOUR PLAN 2) POST YOUR ADDRESS WHERE IT CAN BE SEEN FROM STREET.