Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
Permit Number - T04CM04981
Inspection Description - ELECTRIC - FINAL
Inspection Status - Denied
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/23/2008 | ELECTRIC - FINAL | Denied | ELECTRIC WATER HEATER MODEL GE20P06SAG 19.9 GALLON IS A 2000 WATT UNIT (per data plate and manufacturer web page) PER THE NEC A 25 AMP DISCONNECT WITH #10 AWG CU WIRE FEEDERS IS REQUIRED. THE UNIT IS OPERATING NORMALLY, WITHOUT EXCESS HEAT ON THE 20 AMP BREAKER, BUT IS NOT CODE COMPLIANT. |
|
12/02/2007 | ELECTRIC - FINAL | Partial Approval | Original approval rescinded. Water heater that was thought to be 1500 watt has been reported by DNR to be a 2700 watt device requiring a 30 amp disconnect. |