Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T04CM04958

Parcel: 140290480

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T04CM04958

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
01/14/2005 ELECTRIC - FINAL Approved IVRS - Inspection :*
01/11/2005 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*NOTES: 1) REVISED AND APPROVED DRAWING FOR SERVICE MODIFICATIONS WILL BE REQUIRED PRIOR POWER CLEARANCE. 2) NEUTRAL CONDUCTOR MUST BE INSTALLED TO EACH SERVICE DISCONNECTING MEANS & BOND PER 250.24 5-B 3) SUPPORT & ROUTE GROUNDING ELECTRODE CONDUCTOR FOR X-FORMER TO BLD STRUCTURE PER 250-64 NEC. 4) SERVICE GROUNDING ELECTRODE SYSTEM TO BE TIED IN TO INTERIOR WATER PIPING SYSTEM PER 250-104