Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T04CM04958
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/14/2005 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
01/11/2005 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :*NOTES: 1) REVISED AND APPROVED DRAWING FOR SERVICE MODIFICATIONS WILL BE REQUIRED PRIOR POWER CLEARANCE. 2) NEUTRAL CONDUCTOR MUST BE INSTALLED TO EACH SERVICE DISCONNECTING MEANS & BOND PER 250.24 5-B 3) SUPPORT & ROUTE GROUNDING ELECTRODE CONDUCTOR FOR X-FORMER TO BLD STRUCTURE PER 250-64 NEC. 4) SERVICE GROUNDING ELECTRODE SYSTEM TO BE TIED IN TO INTERIOR WATER PIPING SYSTEM PER 250-104 |