Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T04CM04922

Parcel: 105102420


Addresses:

455 E WETMORE RD


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T04CM04922

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
04/07/2005 ELECTRIC - FINAL Approved IVRS - Inspection :*
04/06/2005 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*1) ADD BUSHINGS TO "L" FLEX FITTINGS. 2) USE CABLE TO CABLE( KEARNEY) FITTING TO ATTACH GROUND WIRES. 3) MARK DISCONNECTS AT REFER CASES WITH CIRCUIT & PANEL #'S