Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T04CM04922
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/07/2005 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
04/06/2005 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :*1) ADD BUSHINGS TO "L" FLEX FITTINGS. 2) USE CABLE TO CABLE( KEARNEY) FITTING TO ATTACH GROUND WIRES. 3) MARK DISCONNECTS AT REFER CASES WITH CIRCUIT & PANEL #'S |