Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T04CM04921
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/04/2005 | PLUMBING - FINAL | Approved | 1) PLBG FINAL IS OK. 2) OK FOR C OFO | |
03/22/2005 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) VENT FOR 2" WASTE LINE SHALL BE LOCATED ABOVE THE TRAP ARM. 2) EXTEND HORIZONTAL VENT ABOVE CEILING UP TO POC OF EXSISTING VENT 3) RE TEST THE SYSTEM |
|
03/21/2005 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SHALL PROVIDE AIR OR WATER TEST ON DWV SYSTEM. 2) SHALL EXPOSE ALL NEW PLBG @ TIME OF INSPECTION |
|
03/19/2005 | PLUMBING - FINAL | Partial Approval | IVRS - Inspection :* 1) FRONT AND REAR MENS & WOMENS RESTROOMS ARE OK. | |
03/13/2005 | PLUMBING - FINAL | Partial Approval | IVRS - Inspection :* 1) SOIL WATER TEST IS OK FOR C.W.V @ CAKE CASE. 2) P.O.C OF NEW BLDG. DRAIN TO EXSISTING BLDG. DRAIN IS OK. OK TO BACKFILL TRENCH. 3) WOMENS RESTROOMS FRONT AND REAR ARE OK FOR FINAL. 4) NOTE: MENS RESTROOMS FRONT AND REAR ONE STALL REQUIRES 15" SIDE WALL CLEARANCE MIN. 5) BACKFLOW PREVENTER FOR PHOTO LAB SHALL BE A 009 WITH DISCHARGE DRAIN. TESTE & CERTIFIED BY FINAL INSPECTION. | |
03/11/2005 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SHALL EXPOSE ALL NEW PLBG. THAT HAS BEEN INSTALLED. 2) AIR TEST IS BELOW 5 LBS MIN |