Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - ABOVE CEILING
Permit Number - T04CM04921
Inspection Description - PLUMBING - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/13/2005 | PLUMBING - ABOVE CEILING | Approved | ||
03/09/2005 | PLUMBING - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SEE NOTES # 1,3,5,6,7 AND NOTE: #3 FROM PREVIOUS INSPECTION ON 03/01/05 2) CANNOT LOCATE A THREADED FITTING IN A CONCEALED LOCATION FOR TEST TEES. 3) AIR PRESSURE TEST FOR DWV REQUIRES A MINIMUM OF 5LBS. 4) SHALL PAY A RE-INSPECTION FEE PRIOR TO THE NEXT INSPECTION. |
|
03/07/2005 | PLUMBING - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* 1) NOT READY FOR INSPECTION | |
03/02/2005 | PLUMBING - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) C.O SHALL BE N A VERTICAL POSITION OR POSITIONED ABOVE CENTER LINE OF TRAD ARM. 2) P-TRAP IS REVERSED @ SINK IN PHOTO AREA. 3) TRAP ARM IS 2" THEN R-TRAP SHALL BE 2". THE TRAP SHALL BE THE SAME SIZE AS THE DRAIN SERVED. 4) SHALL PROVIDE A WATER TEST ON DWV SYSTEM 5) HORIZONTAL VENT ABOVE CEILING HAS BACK PITCH 6) REMOVE C.O TEE IN CEILING 7) EXPOSE P.O.C OF 2" WASTE FOR PHOTO SINK AND VENT P.O.C ABOVE CEILING. 8) SEE NOTE#3 FOR PHOTO LAB |
|
03/01/2005 | PLUMBING - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* 1) EXPANSION TANK NOT SUPPORTED 2) PIPING NOT STRAPPED 3) BACKFLOW DEVICES TO BE TESTABLE TYPE 4) SUBMERSIBLE INLET REQUIRES ? OR EQUAL ONE FOR EYEWASH AND ONE FOR SPRAYER 5) CLEANOUT FOR SINK NOT ACCESSIBLE 6) NO PAN DRAIN FOR WATER HEATER 7) MAY NOT BE A COMPLETE LIST |
|
02/24/2005 | PLUMBING - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) AIR PRESSURE TEST FOR COMBINATION WASTE & VENT SYSTEM IS OK. 2) P.O.C OF C.W.V TO EXISTING BLDG. DRAIN IS OK. 3) OK TO BACKFILL TRENCH. 4) NOTE: SHALO REDUCE 3" P-TRAP@ TOP OF W?? TO 2" FOR BUN?. 5) SHALL PROVIDE A 3" COMBO FOR C.O EXTENTION. 6) SOIL WATER TEST IS OK FOR FLOOR SINK@ CUSTOMER SERVICE AREA. 7) SHALL USE PROPER TRANSITION FROM ABS TO PVC @ P.O.C OF FLOOR SINK. |
|
02/23/2005 | PLUMBING - ABOVE CEILING | Denied | 1) 3/4" C.W SUPPLY GOING UP INTO CEILING IS LOOSE. |