Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/27/2005 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 07/11/2005 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) CHASE NIPPLES TO BE BONDED PER 250.97 2) CONDUIT HAS SHARP METAL EDGES FORM PIPE CUTTER. 3) POLE MA? USE WIRE NUTS LISTED FOR #8 | |
| 06/29/2005 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :*1) VDV CABELING TO BE INSTALLED AS PER 725.6 & 800.6 OK LIGHT FIXTURES, M/C CABLES, AND CONDUIT ABOVE CEILINGS ROOMS # 305,310-314,316-319, 402-410 | |
| 06/15/2005 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK ADMIN BLDG CAN LIGHTS AT ENTRY. PLEASE CALL FOR POLE HEAD INSPECTIONS BEFORE STANDING | |
| 06/10/2005 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) VDV CABLES IN WALLS TO BE INSPECTED BEFORE CLOSING WALLS 2) OK ROOMS 207, 208 AND 200-204 ELECTRIC |
|
| 06/07/2005 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK WALLS ADMINISTRATION BUILDING | |
| 06/06/2005 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK REMAINING COURT YARD SOFFIT CANS AND ENTRY CANS | |
| 06/02/2005 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) REMOVE PLYWOOD TO INSPECT ELECTRIC AS DISCUSSED COVERED WITH OUT INSPECTION. |
|
| 05/19/2005 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK WALLS ROOM 300-303, 205, 206 AND 209-216 2) SUPPORT PVC WITHIN 3' OF FLOORS |
|
| 05/17/2005 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK COURTYARD # 007 REMAINING 3 NORTH SOFFIT. OK COURTYARD # 006 NORTH, WEST, SOUTH SOFFITS | |
| 05/11/2005 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK COURTYARD SOFFIT CANS #007 EAST COURTYARD | |
| 05/05/2005 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) PLEASE COMPLETE #1 OF PREVIOUS INSEPCTION. OK WALL ROOM #'S 304-319 EXCEPT AS NOTED | |
| 05/04/2005 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1) PROPERLY SUPPORT VDV (THERMOSTAT) CABLES 725.6 2) PROTECT PVC AT NOTCHES IN FIREBLOCKS 3) PROTECT M/C CABLES AT STUDS 4) PLEASE VERIFY INTEGRITY OF M/C CABLE WHERE NAIL HAS COME THROUGH SHEATH |
|
| 04/13/2005 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK PVC CONDUITS 1" SITE LIGHTING AND POWE OK WALLS AND M/C CABLE ON CEILING JOIST ROOM 402-411. 1) PROTECT PVC CONDUIT AND M/C CABLES AT STUDS 300.4 |